-Rating (VA/Watts): 8000/7200
-Diagnostics: Full system self test at power up
-UPS Bypass: Yes, ships with MBP11K208
-Dimensions (H x W x D): 259 (6U) x 439 x 762 mm
-Weight: 93 kg
-Warranty: 2 years
-Rail Kit Included: 4-post rail kit and tower pedastals included
-Remote Emergency Power off (REPO): ROO/RPO: Rear deck emergency stop connectors (for remote on/off and power off)
-Input Connectors: Hardwired - see manual for terminal block layout
-Input Cord: None; hardwired
-Input Voltage Range: Full load: 176-276V, Derating: 100-276V
-Nominal Input Voltage: 208V default (200/208/220/230/240/250V)
-Input Frequency: 50/60 Hz
-Input Frequency Range: 60 Hz: 50–70 Hz, 50 Hz: 40–60 Hz
-Input Power Factor: >99
-Nominal Output Voltage: 208V default (200/208/220/230/240/250V)
-Output voltage regulation: ±1% steady-state
-Output Voltage THD: <2% for linear loads
-Output Connectors: (3) NEMA L6-30R, Hardwired
-Power Factor: 0.9
-Transfer Time: 0 ms
-Circuit Breaker: (3) 30A for L6-30R
-Approximate Standard Runtime at 7200 load with no EBM: 5 Minutes
-Optional Extended Battery Module: 9PXEBM240RT
-Battery Description: Sealed, lead-acid; maintenance free
-Maximum number of extended battery modules (EBM): Add up to 5 extended battery modules (EBM) with UPS; add up to 12 EBMs with SC240RT supercharger module
-Battery Management: ABM technology; 3-stage charging extends battery service life by 50% and provides advance warning for battery replacement
-Battery Replacement: Hot-swappable extended battery modules (EBMs); no internal batteries in UPS module
-Start On Battery: Cold-start enabled; first cold start is always forbidden
-User Interface: Graphical display. UPS status in a single view.
-LEDs: 4 status-indicating LEDs
-Communication Ports: RS-232 (RJ45) ports; USB port as standard (HID). 6-foot RS-232 and USB cables included
-Communications Card Slots: Network Card-MS included
-Power Management Software: Eaton Intelligent Power Software Suite CD (included)
General | |
Topology | On-line double conversion with PFC (Power Factor Correction) system |
Configuration | Rack/Tower |
Part Number | 9PX8KiPM and 9PXEBM240 |
Rating (VA/Watts) | 8000/7200 |
Dimensions (H x W x D, mm) | 260 (6U) x 440 x 685 |
Weight (kg) | 84 |
Warranty | 3 years on electronics, 2 years on battery |
Electrical Input | |
Connection | Hardwired - see manual for terminal block layout ![]() |
Input Voltage Range | 176-276V without derating (up to 100–276V with derating) |
Nominal Voltage | 200/208/220/230/240/250V |
Frequency | 50/60 Hz autoselection |
Frequency Range | 40-70 Hz |
Short Circuit Current | 120 A |
THDI | <5% |
Electrical Output | |
Voltages | 200/208/220/230/240/250V +/– 1% |
Voltage THD | < 2% |
Output Receptacles | Hardwired - see manual for terminal block layout ![]() |
Overload Capacity | 102–110% : 120s, 110–125%: 60s, 125–150%: 10s, >150%: 900ms |
Efficiency (Normal Mode) | Up to 95% in Online mode, 98% in Hi-Efficiency mode |
Output Frequency | 50/60 Hz autoselect, frequency converter as standard |
Load Crest Factor | 3:1 |
Battery | |
Battery Management | ABM® and Temperature compensated charging method (user selectable), automatic battery test, deep discharge protection, automatic recognition of external battery units. |
Extended Battery Capability | EBM (3U) |
Communications | |
User Interface | Multilingual graphical LCD display |
Communication Ports | 1 USB port, 1 RS232 serial port (USB and RS232 ports cannot be used simultaneously), 4 dry contacts (DB9), 1 mini terminal block for remote On/Off and 1 for remote power Off, 1 DB15 for parallel operation. |
Communication Slot | 1 slot for Network-MS card, ModBus-MS or Relay-MS cards |
Environmental & Standards | |
Audible Noise | <48dB |
Operating Temperature | 0 to 40°C continuous |
Safety markings | IEC/EN 62040-1, UL 1778, CSA 22.2 |
EMC Markings | IEC/EN 62040 -2 , FCC Class A, IEC/EN 62040-3 (Performance), C-Tick |
Approvals | CE, CB report (TUV), UL (Power Module) |
Tags:
WHAT'S INCLUDED | |
---|---|
Warranty | 3 years on electronics, 2 years on battery |